Chapter 7

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual

Maintenance

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 91 of 170

8. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end

wrench.

9. Disconnect the unit wiring harness connectors from the air/fuel valve and blower motor.

10. Disconnect the wire leads connected to the blower proof switch and blocked inlet switch

(Figures 7-6).

11. Remove the 10-32 x 1/2" long grounding screw from the burner plate (Figures 7-4).

12. Disconnect the gas train from the air/fuel valve by removing the four (4) 1/2” bolts and nuts

(Figure 7-5).

13. Disconnect the inlet air flex hose from the air/fuel valve by loosening the hose clamp.

14. Remove the six (6) 1/4-20 hex nuts and flat washers securing the blower to the burner plate

(Figure 7-6).

15. Remove the blower and air/fuel valve from the burner plate by lifting straight up. Also,

remove the blower gasket, which will be replaced with a new gasket.

16. Remove the eight (8) 3/8-16 nuts from the burner flange (Figure 7-5) using a 9/16” wrench.


BLOWER

PROOF

SWITCH

BLOCKED

INLET

SWITCH

AIR/FUEL

VAVLE

STAGED

IGNITION

ASSEMBLY

FLAME
DETECTOR

BURNER

PLATE

HEX NUTS &

WASHERS (6)

BLOWER

GASKET

IGNITOR-

INJECTOR

BURNER

BLOWER

BURNER

GASKET

BURNER

GASKET

Figure 7-6: Burner Assembly Exploded View

NOTE

The burner assembly is heavy, weighing approximately 30 pounds.

17. Remove the burner assembly from burner flange by pulling straight up.

18. Remove and replace the two (2) burner gaskets.