TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT

INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

INTERLOCK

OPEN

1. Interlock jumper not installed or

removed

2. Energy Management System does

not have boiler enabled.

3. Device proving switch hooked to

interlocks is not closed.

1. Check for a jumper properly installed across the interlock terminals in the

I/O box

2. If there are two external wires on these terminals check any Energy

Management system to see if they have the units disabled (a jumper may
be temporarily installed to see if the interlock circuit is functioning).

3. Check that proving switch for any device hooked to the interlock circuit is

closing and that the device is operational.

LINE

VOLTAGE

OUT OF

PHASE

1. Line and Neutral switched in AC

Power Box.

2. Incorrect power supply transformer

wiring.

1. Check hot and neutral in AC Power Box to ensure they are not reversed

2. Check transformer wiring, in AC Power Box, against the power box

transformer wiring diagram to ensure it is wired correctly

LOW GAS

PRESSURE

1. Incorrect supply gas pressure.


2. Defective Low Pressure Gas Switch

1. Measure gas pressure upstream of the supply gas regulator with the unit

firing. Refer to paragraph 2.7.1 to ensure that the gas pressure is correct
for the type of fuel and gas train being used.

2. Measure gas pressure at the low gas pressure switch. If it is greater than

2.6” W.C. (or 2.1"W.C. for propane), measure continuity across the switch
and replace if necessary.

LOW WATER

LEVEL

1. Insufficient water level in system

2. Defective water level circuitry.


3. Defective water level probe.

1. Check system for sufficient water level.

2. Test water level circuitry using the Control Box front panel LOW WATER

TEST and RESET buttons. Replace water level circuitry if it does not
respond.

3. Check continuity of probe end to the shell, change probe if there is no

continuity.

MODBUS

COMM
FAULT

1. Boiler not seeing information from

Modbus network

1. Check network connections. If fault persists, contact qualified Service

Personnel.

PRG SWTCH

CLOSED

DURING

IGNITION

1. A/F Valve rotated open to purge and

did not rotate to ignition position.

1. Start the unit. The Air/Fuel Valve should rotate to the purge (open) position,

then back to ignition position (towards closed) during the ignition cycle. If
the valve does not rotate back to the ignition position, check the Air/Fuel
Valve calibration. If calibration is okay, the problem may be in the Air/Fuel
Valve or the Control Box. Refer fault to qualified service personnel.