Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 106

background image

Chapter 8

Benchmark 2.0LN Low NOx Boiler

GF-123

Troubleshooting Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 106 of 170 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

PR1 08/20/12

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

STEPPER MOTOR

FAILURE

1. Air/Fuel Valve out of calibration.






2. Air/Fuel Valve unplugged.

3. Loose wiring connection to the

stepper motor.

4. Defective Air/Fuel Valve stepper

motor.

5. Defective Power Supply Board or

fuse

6. Defective IGST Board

1. Refer to GF-112 and perform Stepper Test (para. 6.3.5) to

ensure stepper motor rotates properly between the 0% (fully
closed) and 100% (fully open) positions. Verify that the VALVE
POSITION bargraph and the dial on the Air/Fuel Valve track
each other to indicate proper operation. If operation is not
correct, perform the Stepper Feedback Calibration (GF-112,
paragraph 6.2.1).

2. Check that the Air/Fuel Valve is connected to the Control Box.

3. Inspect for loose connections between the Air/Fuel motor and

the wiring harness.

4. Replace stepper motor.

5. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board

6. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board