6 configuration menu, 6 configuration menu -40, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual
Page 40: Gf-123

Chapter 2
Benchmark 2.0LN Low NOx Boiler
GF-123
Installation
Installation, Operation and Maintenance Manual
OMM-0046_0E
Page 3-40 of 170
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the valid password has been entered. Setpt is
required for operation in the Constant Setpoint mode. The remaining options in this menu
require the valid password to be entered, prior to changing existing entries. This menu
contains a number of other configuration settings which may or may not be displayed,
depending on the current operating mode setting.
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory-Set in accordance with the
requirements specified for each individual order. Therefore, under normal operating
conditions, no changes will be required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Boiler, BMK Boiler LN,
BMK Boiler Dual, KC Water
Heater, KC Water Heater LN,
Water Heater 2010
BMK Boiler
LN
Unit Size
0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
3.0 MBTU, 3.5 MBTU
4.0 MBTU, 5.0 MBTU
6.0 MBTU
2.0 MBTU
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F