5 setup menu, 5 setup menu -39, Gf-123 – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual
Page 39: Benchmark 2.0ln low nox boiler

GF-123
Benchmark 2.0LN Low NOx Boiler
Chapter 2
OMM-0046_0E
Installation, Operation and Maintenance Manual
Installation
PR1 08/20/12
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288
Page 39 of 170
NOTE
The Outdoor Temp display item shown with an asterisk in Table 3-2 will
not be displayed unless the Outdoor Sensor function has been enabled
in the Configuration Menu (Table 3-4).
Table 3-2: Operating Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Status Message
Active Setpoint
40°F
240°F
AIR Temp
-70°F
245°F
Outdoor Temp*
-70°F
130°F
Valve Position In
0%
100% Valve
Position
Flame Strength
0%
100%
Run Cycles
0
999,999,999
Run Hours
0
999,999,999
Fault Log
0
19
0
3.5 SETUP MENU
The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-
out after 1 hour. Therefore, the correct password must be reentered when required. In
addition to permitting password entries, the Setup Menu is also used to enter date and time,
units of temperature measurements and entries required for external communication and
control of the unit via the RS-232 port. A view-only software version display is also provided
to indicate the current Control Box software version.
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
0
9999
0
Language
English
English
Time
12:00 am
11:59 pm
Date
01/01/00
12/31/99
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400, 4800, 9600, 19.2K
9600
Software Version
Ver 0.00
Ver 9.99