Chapter 3
Benchmark 2.0LN Low NOx Boiler
GF-123
Operation
Installation, Operation and Maintenance Manual
OMM-0046_0E
Page 42 of 170
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12
*CAUTION!
DO NOT CHANGE the Analog Output Menu Item from its Default setting
(Valve Position 0-10V).
3.7 TUNING MENU
The Tuning Menu items in Table 3-5 are Factory set for each individual unit. Do not change
these menu entries unless specifically requested to do so by Factory-Trained personnel.
3.8 COMBUSTION CAL MENU
The Combustion Cal (Calibration) Menu items in Table 3-6 are used to vary the speed of the
unit’s blower motor based on air temperature and air density at prescribed Air/Fuel Valve
positions (% open). This is accomplished by providing a DC drive voltage to the motor which
adjusts the rotational speed of the blower to maximize combustion efficiency and ensure the unit
conforms to the Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions specified in
Chapter 4. The valve positions (%) and default drive voltages are listed in Table 3-6.
Table 3-5: Tuning Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Prop Band
1°F
120°F
70°F
Integral Gain
0.00
2.00
1.00
Derivative Time
0.0 min
2.00 min
0.00 min
Reset Defaults?
Yes, No, Are You Sure?
No
Table 3-6: Combustion Cal Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
CAL Voltage 16%
.25
8.20
1.80v
CAL Voltage 30%
.25
8.20
3.20v
CAL Voltage 45%
.25
8.20
3.70v
CAL Voltage 60%
.25
8.20
3.80
CAL Voltage 80%
.25
8.20
4.60
CAL Voltage 100%
.25
8.20
6.00
SET Valve Position
0%
100%
0%
Blower Output
Monitor Blower Output
Voltage
.00