Chapter 4

Benchmark 2.0LN Low NOx Boiler

GF-123

Initial Start-Up

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 56 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

31. The oxygen level at the 60% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-3: Combustion Oxygen Levels for a

60% Air/Fuel Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

5.7 %

<50 ppm

<30 ppm

32.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

33. Once the oxygen level is within the specified range at 60%, press the ENTER key to store

the selected blower output voltage for the 60% valve position.

34.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

35. Press the CHANGE key. SET Valve Position will begin to flash.

36.

Press the ▼ arrow key until the SET Valve Position reads 45%, then press the ENTER key.

37.

Press the ▼ arrow key until CAL Voltage 45% is displayed.

38. Press the CHANGE key. CAL Voltage 45% will begin to flash.

39. The oxygen level at the 45% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-4: Combustion Oxygen Levels for a

45% Air/Fuel Valve Position

Oxygen %

± 0.2

Carbon Monoxide NOx

7.2 %

<50 ppm

<30 ppm

40.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

41. Once the oxygen level is within the specified range at 45%, press the ENTER key to store

the selected blower output voltage for the 45% valve position.

42.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

43. Press the CHANGE key. SET Valve Position will begin to flash.

44.

Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.

45.

Press the ▼ arrow key until CAL Voltage 30% is displayed.

46. Press the CHANGE key. CAL Voltage 30% will begin to flash.

47. The oxygen level at the 30% valve position should be as shown in Table 4-5. Also, ensure

that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Table 4-5: Combustion Oxygen Levels for a

30% Air/Fuel Valve Position

Oxygen %

± 0.2

Carbon Monoxide NOx

8.0 %

<50 ppm

<30 ppm