Chapter 4

Benchmark 2.0LN Low NOx Boiler

GF-123

Initial Start-Up

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 50 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

4.2.1 Required Tools & Instrumentation

The following tools and instrumentation are necessary to perform combustion calibration of the
unit:

Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and
Nitrogen Oxide (NOx) resolution to 1PPM.

16 inch W.C. manometer or equivalent gauge and plastic tubing.

1/4" NPT-to-barbed fittings for use with gas supply manometer or gauge.

Small and large flat blade screwdrivers.

Tube of silicone adhesive

4.2.2 Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to calibrate the gas pressure to be monitored on
the downstream side of the SSOV during the Combustion Calibration procedures described in
paragraph 4.4.

The gas supply manometer is installed at the downstream location on the 1/4” NPT port shown
in Figure 4-1. Note that a 1/4” plug must be removed from the port in order to install the
manometer.

Figure 4-1: Manometer Installation Location

NOTE

If a second 16” W.C. manometer is available, it can be installed in the
SSOV downstream location to provide continuous monitoring at both the
upstream and downstream ports of the SSOV. However, if only one is
available, the RSI Regulator must be calibrated first, prior to moving the
manometer to the downstream location.

SSOV

GAS

INLET

TO AIR/FUEL

VALVE

MANUAL

SHUT-OFF

VALVE

(Shown open)

RSI GAS

VALVE

(Shown Closed)

RSI

REGULATOR

1/4” NPT PLUG

(Install manometer here for

RSI Regulator Calibration)

1/4” NPT PLUG

(Install manometer

here for Combustion

Calibration)