Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 47

background image

GF-123

Benchmark 2.0LN Low NOx Boiler

Chapter 3

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual

Operation

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 47 of 170

Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position. Refer
to Table 3-7 for the relationship between the energy input and Air/Fuel Valve position for a unit
running on natural gas.

Table 3-7. Relationship Between Air/Fuel Valve Position and Energy Input For

Unit Running On Natural Gas

Air/Fuel Valve Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0

0

0

10%

0

0

18%

(Stop Level)

100,000

5.0%

20%

134,000

7%

30%

349,000

17%

40%

631,000

32%

50%

893,000

45%

60%

1,150,000

58%

70%

1,410,000

71%

80%

1,610,000

81%

90%

1,830000

92%

100%

2,000,000

100%