Aerco, Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual
Page 151: Appendix g, Nstallation , operation and maintenance manual, Piping drawings, Legend

GF-123
Benchmark 2.0LN Low NOx Boiler
Appendix G
OMM-0046_0E
I
nstallation, Operation and Maintenance Manual
Piping Drawings
PR1 08/20/12
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288
Page 151 of 170
5)
THIS IS A TYPICAL INSTALLATION DRAWING
.
LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED
.
CONVENIENT FLOOR DRAIN
.
RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT
18
'' ABOVE FLOOR
.
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS
.
ALL PIPING AND
ELECTRIC CONNECTIONS
(SERVICE SWITCHES
, CONDUIT BOXES
) SHOULD LIKEWISE BE
6"
AWAY FROM SIDE PANELS
.
1)
FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER
, SEE DIMENSIONAL DRAWING
(AP
-A
-797
).
3)
ALL
(*)
ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY
.
NOTES
:
AIR SEPARATOR
AUTOMATIC AIR VENT
1-
1/
2"
NPT
DRAIN CONN
.
LINE SIZE
BYPASS
BACKFLOW PREVENTER
DIAPHRAGM TYPE EXPANSION TANK
WATER
SUPPLY
* CONDENSATE
DRAIN TRAP
P&
T
PRESSURE REDUCING FILL VALVE
CHECK VALVE (TYP
.)
HEATING SYSTEM SUPPLY
SYSTEM PUMP
P&
T
RELIEF
VALVE
(TYP
.)
HEATING SYSTEM RETURN
* 2
" MANUAL
SHUTOFF VALVE
GAS SUPPLY
2)
SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY
, BY GRAVITY
, TO A
4)
LOCATE WATER INLET AND OUTLET FITTINGS
(i.
e.
UNIONS
, ELBOWS
, ETC
.)
A MINIMUM OF
6''
FROM BOILER
NORTHVALE
, NJ
07647
INTERNATIONAL
, INC
.
APPD
.
DWN
.BY
SCALE
DATE
DATE
CZ
NTS
102307
AERCO
SD
-A
-672
TEMPERATURE GAUGE
P&
T
PRESSURE
&
BALANCING VALVE
ISOLATION VALVE
UNION
Y STRAINER
LEGEND
BENCHMARK
2.
0
MIL
. BTU LOW NOx
GAS FIRED BOILER
MULTIPLE UNIT INSTALLATION
6)
WHEN AVAILABLE GAS PRESSURE IS GREATER THAN
2.
0
PSIG
, A LOCK
-UP STYLE REGULATOR MUST BE INSTALLED
DOWNSTREAM OF THE
2"
MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO
2.
0
PSIG
.
REV
C
AT MAXIMUM BTU
/HR INPUT
,
MAINTAIN MIN
. NATURAL GAS
PRESS
. AT
4.
0"
W
.C
.(FM GAS TRAIN
)/
5.
0"
W
.C
.(IRI GAS TRAIN
);
MAX
. GAS PRESSURE
=
2.
0
PSIG
(SEE NOTE
6).
7)
A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS
, REGARDLESS OF SUPPLY PRESSURE
.
SEE DIAGRAM
1
DRIP TRAP
DRIP TRAP
* 2
" MANUAL
SHUTOFF VALVE
MAINTAIN A REGULATED 4.
0"
W
.C
. (
NAT
. GAS
, FM
)/
5.
0"
W
.C
. (
NAT
. GAS
, IRI
)
GAS PRESSURE AT MAX BTU
/HR INPUT
GAS SUPPLY
(TO BOILER
)
(SEE NOTE
7)
Diagram
1