Benchmark 2.0LN Low NOx Boiler

Chapter 2

OMM-0046_0E

Installation, Operation and Maintenance Manual

Installation

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 35 of 170

Table 3-1 Operating Controls, Indicators and Displays

ITEM

NO.

CONTROL, INDICATOR

OR DISPLAY

FUNCTION

1

LED Status Indicators

Four Status LEDs indicate the current operating status as
follows:

COMM

Lights when RS-232 communication is occurring

MANUAL

Lights when the unit is being controlled using the front panel
keypad.

REMOTE

Lights when the unit is being controlled by an external signal
from an Energy Management System

DEMAND

Lights when there is a demand for heat.

2

OUTLET
TEMPERATURE

Display

3–Digit, 7–Segment LED display continuously displays the
outlet water temperature. The °F or °C LED next to the
display lights to indicate whether the displayed temperature is
in degrees Fahrenheit or degrees Celsius. The °F or °C blinks
when operating in the Deadband Mode.

3

VFD Display

Vacuum Fluorescent Display (VFD) consists of 2 lines each
capable of displaying up to 16 alphanumeric characters. The
information displayed includes:
Startup Messages
Fault Messages
Operating Status Messages
Menu Selection

4

RS-232 Port

Port permits a Laptop Computer or External Modem to be
connected to the unit’s Control Panel.

5

FAULT Indicator

Red FAULT LED indicator lights when a boiler alarm
condition occurs. An alarm message will appear in the VFD.

6

CLEAR Key

Turns off the FAULT indicator and clears the alarm message
if the alarm is no longer valid. Lockout type alarms will be
latched and cannot be cleared by simply pressing this key.
Troubleshooting may be required to clear these types of
alarms.

7

READY Indicator

Lights ON/OFF switch is set to ON and all Pre-Purge
conditions have been satisfied.

8

ON/OFF Switch

Enables and disables boiler operation.

9

LOW WATER LEVEL

TEST/RESET
Switches

Allows operator to test operation of the water level monitor.
Pressing TEST opens the water level probe circuit and
simulates a Low Water Level alarm.
Pressing RESET resets the water level monitor circuit.
Pressing the CLEAR key (item 6) resets the display.