Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 61

background image

GF-123

Benchmark 2.0LN Low NOx Boiler

Chapter 4

OMM-0046_0E

I

nstallation, Operation and Maintenance Manual

Initial Start-Up

PR1 08/20/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 61 of 170

41. Once the oxygen level is within the specified range at 45%, press the ENTER key to store

the selected blower output voltage for the 45% valve position.

42.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

43. Press the CHANGE key. SET Valve Position will begin to flash.

44.

Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER key.

45.

Press the

▼ arrow key until CAL Voltage 30% is displayed.

46. Press the CHANGE key. CAL Voltage 30% will begin to flash.

47. The oxygen level at the 30% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-11: Combustion Oxygen Level at

30%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

8.0 %

<50 ppm

<30 ppm

48.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

49. Once the oxygen level is within the specified range at 30%, press the ENTER key to store

the selected blower output voltage for the 30% valve position.

50.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

51. Press the CHANGE key. SET Valve Position will begin to flash.

52.

Press the ▼ arrow key until the SET Valve Position reads 20%, then press the ENTER key.

53.

Press the ▼ arrow key until CAL Voltage 16% is displayed.

54. Press the CHANGE key. CAL Voltage 20% will begin to flash.

55. The oxygen level at the 20% valve position should be as shown below. Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values shown.

Table 4-12: Combustion Oxygen Level at

20%

Valve Position

Oxygen %

± 0.2

Carbon Monoxide

NOx

8.6 %

<50 ppm

<30 ppm

56.

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow key
decreases the oxygen level.

57. Once the oxygen level is within the specified range at 20%, press the ENTER key to store

the selected blower output voltage for 20% valve position.

58. This completes the Propane Combustion Calibration procedure.