Chapter 3

Benchmark 2.0LN Low NOx Boiler

GF-123

Operation

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 46 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

25

TO BLOWER

AIR IN

DIAL
(DETAIL “A”)

STEPPER

MOTOR

DETAIL “A”

Figure 3-6: Air/Fuel Valve In Ignition Position

6. Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be turned

off one second after flame is detected.

7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame strength

will be indicated. After 5 seconds, the current date and time will be displayed in place of the
flame strength.

8. With the unit firing properly, it will be controlled by the temperature controller circuitry. The

boiler’s VALVE POSITION will be continuously displayed on the front panel bargraph.

Once the demand for heat has been satisfied, the Control Box will turn off the dual SSOV gas
valves. The blower relay will be deactivated and the Air/Fuel Valve will be closed. Standby will
be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:

Natural Gas:

• Start Level: 22%

• Stop Level: 18%

Propane:

• Start Level: 24%

• Stop Level: 20%

Normally, these settings should not require adjustment.