beautypg.com

Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 90

background image

Chapter 7

Benchmark 2.0LN Low NOx Boiler

GF-123

Maintenance

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 90 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

Part No.

Description

81101

Burner Gaskets (2)

81048

Flame Detector Gasket

81068

Blower Gasket

To inspect or replace the burner assembly:

1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from

the unit and turn off the gas supply.

2. Remove the side and top panels from the unit.

3. Disconnect the lead wire from the flame detector installed on the burner plate. See Figure 7-

5.

IGNITOR-

INJECTOR

3/8-16

NUTS (8)

BLOWER

BURNER

PLATE

AIR/FUEL

VALVE

FLAME

DETECTOR

STAGED

IGNITION

ASSEMBLY

1/2” BOLTS & NUTS (4)

CONNECT AIR/FUEL VALVE

TO GAS TRAIN

GROUNDING

SCREW

(10-32 x 1/2" LG.)

Figure 7-5:

Burner Assembly Mounting Details

4. Remove the two (2) screws securing the flame detector to the plate. The flame detector is

secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.

5. Remove the flame detector and gasket from the burner plate.

6. Disconnect the cable from the igniter-injector.

7. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector

tube of the igniter-injector to the elbow of the staged ignition assembly (see Figure 7-2).
Disconnect the staged ignition assembly from the igniter-injector.

IMPORTANT

Prior to removing the igniter-injector, note the position of the gas injector
tube relative to the burner plate and blower. This is necessary to ensure
that the igniter injector is reinstalled in the proper orientation when it is
reconnected to the staged ignition assembly.