Appendix G

Benchmark 2.0LN Low NOx Boiler

GF-123

Piping Drawings Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 152 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

5)

THIS IS A TYPICAL INSTALLATION DRAWING

.

LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED

.

CONVENIENT FLOOR DRAIN

.

RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT

18

''

ABOVE FLOOR

.

FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS

.

ALL PIPING AND

ELECTRIC CONNECTIONS

(SERVICE SWITCHES

, CONDUIT BOXES

) SHOULD LIKEWISE BE

6"

AWAY FROM SIDE PANELS

.

1)

FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER

, SEE DIMENSIONAL DRAWING

(AP

-A

-797

).

3)

ALL

(*)

ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY

.

NOTES

:

2)

SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY

, BY GRAVITY

, TO A

4)

LOCATE WATER INLET AND OUTLET FITTINGS

(i.

e.

UNIONS

, ELBOWS

, ETC

.)

A MINIMUM OF

6''

FROM BOILER

NORTHVALE

, NJ

07647

INTERNATIONAL

, INC

.

APPD

.

DWN

.BY

SCALE

DATE

DATE

JK

NTS

102307

AERCO

SD

-A

-674

TEMPERATURE GAUGE

P

&

T

PRESSURE

&

BALANCING VALVE

ISOLATION VALVE

UNION

Y STRAINER

LEGEND

BENCHMARK

2.

0

MIL

. BTU LOW NOx

GAS FIRED BOILER

3-

UNIT INSTALLATION

(2

ZERO

-SIDE

&

1

SEPARATE

)

*

CONDENSATE

DRAIN TRAP

1-

1/

2"

NPT

DRAIN CONN

.

BACKFLOW PREVENTER

DIAPHRAGM TYPE EXPANSION TANK

LINE SIZE

BYPASS

SUPPLY

WATER

HEATING SYSTEM SUPPLY

PRESSURE REDUCING FILL VALVE

P

&

T

SYSTEM PUMP

CHECK VALVE (TYP

.)

AUTOMATIC AIR VENT

AIR SEPARATOR

GAS SUPPLY

HEATING SYSTEM RETURN

*

2"

MANUAL

SHUTOFF VALVE

P

&

T

RELIEF VALVE

(TYP

.)

REV

C

DOWNSTREAM OF THE

2"

MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO

2.

0

PSIG

.

6)

WHEN AVAILABLE GAS PRESSURE IS GREATER THAN

2.

0

PSIG

, A LOCK

-UP STYLE REGULATOR MUST BE INSTALLED

7)

A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS

, REGARDLESS OF SUPPLY PRESSURE

.

SEE DIAGRAM

1

AT MAXIMUM BTU

/HR INPUT

,

MAINTAIN MINIMUM NATURAL GAS PRESSURE AT 4.

0"

W

.C

.(

FM GAS TRAIN

)/

5.

0"

W

.C

.(

IRI GAS TRAIN

);

MAX

. GAS PRESSURE

=

2.

0

PSIG

. (

SEE NOTE

6)

DRIP TRAP

*

2"

MANUAL SHUTOFF

VALVE

MAINTAIN A REGULATED 4.

0"

W

.C

. (

NAT

. GAS

, FM

)/

5.

0"

W

.C

. (

NAT

. GAS

, IRI

)

GAS PRESSURE AT MAX BTU

/HR INPUT

GAS SUPPLY

(TO BOILER

)

(SEE NOTE

7)

Diagram

1

P

&

T

DRIP TRAP