GF-123
Benchmark 2.0LN Low NOx Boiler
Chapter 2
OMM-0046_0E
Installation, Operation and Maintenance Manual
Installation
PR1 08/20/12
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288
Page 41 of 170
Table 3-4. Configuration Menu - Continued
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
195°F
195°F
Temp Hi Limit
40°F
210°F
195°F
Max Valve Position
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.
Failsafe Mode
Shutdown or Constant Setpt
Shutdown
*Analog Output
(See CAUTION at
end of Table 3-4 )
Off, Setpoint, Outlet Temp,
Valve Position 4-20 mA,
Valve Position 0-10V
*Valve
Position
0-10V
Low Fire Timer
2 sec.
600 sec.
2 sec.
Setpt Limiting
Enabled or Disabled
Disabled
Setpt Limit Band
0°F
10°F
5°F
Network Timeout
5 Sec
999 Sec
30 Sec
HI DB Setpt EN
0%
100%
30%
Demand Offsert
0
25
10
Deadband High
0
25
2
Deadband Low
0
25
2
*CAUTION:
DO NOT CHANGE the Analog Output Menu Item from its Default setting
(Valve Position 0-10V).