Chapter 6

Benchmark 2.0LN Low NOx Boiler

GF-123

Safety Device Tests

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 80 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

ACTUATOR

COVER

SCREW

SSOV

ACTUATOR

COVER

Figure 6-4: SSOV Actuator Cover Location

6.10 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set the

valve position between 25% and 30%.

2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it and

then lift up (see Figure 6-5).

3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.

5. The unit should begin it’s start sequence, then shut down and display PRG SWITCH OPEN

DURING PURGE.

6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should

restart.

6.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the
switch, proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF position.

2. Place the unit in Manual Mode and set the valve position between 25% and 30%.

3. Remove the Air/Fuel Valve cover (Figure 6-5) by rotating the cover counterclockwise to

unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-6).

5. Initiate a unit start sequence.

6. The unit should begin its start sequence and then shut down and display IGN SWITCH

OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should

restart.