Wiring to the devicenet controller (lk-dn100), Wiring to the devicenet controller, Lk-dn100) -6 – KEYENCE LK-CC100/DN100 User Manual
Page 42: Typical connection, Connecting terminators

3-6
3
3 Connecting to DeviceNet
Wiring to the DeviceNet controller (LK-DN100)
The LK-DN100 field network connector (terminal block) is to be wired as explained below.
Connect the cable by matching the color of the wires to the colors on the sticker affixed to the
DeviceNet connector.
Typical connection
Refer to the manual for the DeviceNet master unit for wiring details.
Connecting terminators
A terminator must be connected to both ends of the
trunk line. The terminators must be connected to
reduce signal reflection and stabilize communication.
Terminator resistance: metal-film resistor 121 ohms,
1%, 1/4W
The terminators must be connected, otherwise, DeviceNet will
not communicate properly.
Terminal
name
Wire
color
Function
V+
Red
Communication power supply (24 VDC input)
CAN_H
White
Communication signal High
SHIELD
Exposed Shield
CAN_L
Blue
Communication signal Low
V-
Black
Communication power supply (0 VDC input)
V+
CAN H
SHIELD
CAN L
V-
NOTE
Terminator
Terminator
LK-DN100
Other unit
Other unit
Master node
Other unit
LK-DN100
CAN H
CAN L
Terminator
V+
CAN H
SHIELD
CAN L
V-
NOTE