4 command parameter list, Co mm u ni c a ting w ith t he fd -s s er ie s – KEYENCE DL-CL1 User Manual
Page 54

3-4 Command Parameter List
3-26
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Co
mm
u
ni
c
a
ting
w
ith t
he FD
-S
s
er
ie
s
3
For the communication methods using motion command parameters, see
a Motion Command to a Sensor Amplifier" (page 3-20).
Attribute R: Read; C: Motion command
nn: ID number of sensor amplifier. Example: For nn05h and ID13, then 0D05h.
Setting/status command parameters
For the communication methods using setting/status parameters, see
Writing Settings or Status of a Sensor Amplifier" (page 3-21).
Attribute R: Read; W: Write; R/W: Read/Write
nn: ID number of sensor amplifier. Example: For nn41h and ID13, then 0D41h.
The data type is DINT (32-bit singed integer).
Data
category
(HEX)
Data
number
(HEX)
Name
Description
Attribute
00
nn00
Group-0 entry count
FD-SA*A:6, FD-SA*:5
R
nn01
Zero adjustment request
Executes zero adjustment.
C
nn02
Integrated fl ow quantity reset
request
Resets integrated fl ow quantity.
C
nn03
Instantaneous fl ow hold value
reset request
Resets instantaneous fl ow hold value.
C
nn04
Temperature hold value reset
request
Resets temperature hold value.
C
nn05
Initial reset request (ALL)
Resets all settings of the sensor amplifi er to
the factory default settings.
C
nn06
Initial reset (SLct)
Resets the sensor amplifi er to the factory
default settings., except for some items such
as zero adjustment.
Available only to FD-S (version A).
C
Data
category
(HEX)
Data
number
(HEX)
Name
Description
Attribute
Sensor head
Default
value
Parameter range
00
nn20
Group-1 entry
count
R
-
21
nn21
Error state
*1
R
-
-
Bit 0: Always 0
Bit 1: Head connection error
Bit 2: Overcurrent Error
Bit 3: EEPROM Error
Bit 4: Dry water error
Bit 5: Backflow error
Bits 6 - 8: Always 0
Bit 9: Drive gain error
Bit 10: Temperature lower error
Bit 11: Temperature high error
Bits 12 to 15: Always 0
nn22 to
nn23
System reserved
nn24
Output terminal
state
*2
R
-
-
Bit 0: Output 1
Bit 1: Output 2
Bit 2: Output 3
Bits 3 to 15: Always 0