P. 3-10, Device maps for, 2 device maps – KEYENCE DL-CL1 User Manual
Page 38: Co mm u ni c a ting w ith t he fd -s s er ie s

3-2 Device Maps
3-10
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-S) -
Co
mm
u
ni
c
a
ting
w
ith t
he FD
-S
s
er
ie
s
3
Number [n] denotes the first data memory number assigned to the DL-CL1.
*1
See
"Reading Current Values (Instantaneous Flow Rate) from Sensor Amplifiers" (page 3-18).
*2
See
"Reading/Writing Settings or Status of a Sensor Amplifier" (page 3-21).
See
"Issuing a Motion Command to a Sensor Amplifier" (page 3-20).
*3
See
"Command Parameter List" (page 3-24).
The following device maps are used when the operating mode is monitor mode 2, full
mode 1, or full mode 2.
In cases of small-memory mode 1, small-memory mode 2, and monitor mode 1,
see
"Device Maps for Small-Memory Mode 1, Small-Memory Mode 2, and Monitor
Remote Input RX (DL-CL1 -> Master Station)
Device Maps for Monitor Mode 2, Full Mode 1, and Full Mode 2
Operating
mode
Device no.
(HEX)
Name
Communication
method
Description
Reading range
Monitor mode
2
Full mode
1
Full mode
2
RX[n] + 00
to 03
Output-1
ID 01 to ID 04
*1
Sends the output-1 state (ON/OFF) of the
sensor amplifi er.
The output-1 of each sensor amplifi er (ID 01
to ID 04) corresponds to each RX.
0: OFF
1: ON
RX[n] + 0F Error state
-
The DL-CL1 is not communicating properly
with the sensor amplifi er, or an error exists
with the sensor amplifi er.
If an error exists, the error code is stored in
error code (RWr[n] + 00).
0:No Error
1:Error
RX[n] + 10
to 13
Output-2
ID 01 to ID 04
*1
Sends the output-2 state (ON/OFF) of the
sensor amplifi er.
The output-2 of each sensor amplifi er (ID 01
to ID 04) corresponds to each RX.
0: OFF
1: ON
RX[n] + 1F (Not used)
-
-
-
RX[n] + 20
to 23
Output-3
ID 01 to ID 04
*1
Sends the output-3 state (ON/OFF) of the
sensor amplifi er.
The output-3 of each sensor amplifi er (ID 01
to ID 04) corresponds to each RX.
0: OFF
1: ON
RX[n] + 2F System reserved
-
Unusable
RX[n] + 30
to 33
(Not used)
-
-
-
RX[n] + 3F
System reserved
-
Unusable