Command format *15G1A
Response format 15G1A15
3. Write “VLT” as units of measure into the EEPROM of the meter in the point-to-point mode:
Command format *W1F564C54
Response format W1F
where 56, 4C, 54 are the three HEX ASCII values for V, L, and T respectively.
4. Read alarm status character from the meter number 15 HEX:
Command format *15U01
Response format 15U01@
where “@” is the alarm status character, decoded using Table 8.5 or 8.6.
5. Enable setpoints number 3 and 4 in point-to-point mode:
Command format *E01
Response format E01
6. Hold display value on meter number 15 HEX:
Command format *15D04
Response format 15D04
7. Cold reset (reset 1) in point-to-point mode:
Command format *Z04
Response format Z04
8. Publish measurement string from the meter in point-to-point mode:
Command format *V01
Response format V01 567.891 567.880 712.345 110.765
9. Publish current reading value from the meter number 15 HEX in multipoint mode:
Command format *15X01
Response format X01 567.891
10. Read block of data from EEPROM in point-to-point mode:
Command format *R42
Response format R42271100010001EO3E003F
11. Display “HELLO” onto the meter number 15 HEX in multipoint mode:
Command format *15Y01HELLO
Response format 15Y01
8.10 Examples: Rate Meter/Totalizers/Batch
The following are examples of the different commands and their proper responses from rate meter/totalizers,
batch. For the following examples assume that:
a) echo
mode
CF 125 INFINITY SC GUIDE
28
M1519/N/0605
b) “*” as the recognition character of the meter