Troubleshoot the Controller Chapter 7

Install an I/O Force (Force an I/O Value

1. Go online with the controller and open the routine that contains the tag that you want to force.

2. Right-click the tag and choose Monitor.

3. If necessary, click the + sign of the tag to show the value that you want to force (for example, the

BOOL value of a DINT tag).

4. Install the force value:

5. From the Forces menu, choose I/O Forcing > Enable All I/O Forces and click

.

To force a

Do this

BOOL value

Right-click the tag and choose Force ON or Force OFF.

Integer or REAL value

In the Force Mask column for the tag, type the value to which
you want to force the tag and press [Enter}.