Program a Project Online Chapter 8
Start a Pending Edit
1. For relay ladder, click (select) the rung that you want to edit.
2. Start a pending edit.
Relay ladder
Test edits
When you accept your pending edits, the software downloads them to the
controller and marks them as test edits but the controller continues to execute the
original logic. You then manually switch execution to the test edits or back to the
original logic (test and untest the edits).
In relay ladder, if you delete a rung the software immediately marks it as a test
edit (upper-case 'D' character).
Function block
Structured text
SFC
This marker
Means
Description
- or -
If you
Then
Test the edits
• Execution switches to the test edits (all test edits
execute).
• Outputs in the original logic stay in their last state
unless executed by the test edits (or other logic).
• In an SFC, the chart resets to the initial step and
stored actions turn off.
Untest the edits
• Execution switches back to the original logic.
• Outputs in the test edits stay in their last state
unless executed by the original logic (or other
logic).
• In an SFC, the chart resets to the initial step and
stored actions turn off.
Relay Ladder
Function Block, Structured Text, SFC