Figure a.9 sh, Attention – Rockwell Automation 1394 SERCOS Interface Multi-Axis Motion Control System User Manual
Page 74

Publication 1394-IN024B-EN-P — February 2004
A-10
Interconnect Diagrams
Figure A.9
Non-Isolated Series Start/Stop String
1
When bypassing the TB1/TB2 terminations, ensure that unshielded motor power conductors are kept as short as
possible at the drive, as they will radiate high levels of electrical noise.
Note: Refer to Figure 1.3 for the location of the TB1/TB2 connectors
and pin-out diagram.
Axis 0
TB1
Axis 2
Axis 3
Motor brake
filter (Series C)
Motor thermal
switch filter
(Series C)
TB2
1394C-AM
xx
TB2
1394C-AM
xx
Axis 1
TB1
TB2
1394C-AM
xx
TB1
TB2
1394C-AM
xx
1 2 3 4
1 2
3 4
Motor thermal switch wiring for
1326AB/AS motor resolver feedback
Drive System OK
Relay
1
2
3
4
5
6
7
8
9
10
1394 SERCOS Interface
Control Board
1394C-SJT
xx-D
Relay Output
Connector
24V AC/DC
STOP
START
CR1
CR1
CR1
M1
3 4
3 4
3 4
3 4
Refer to Attention statement below
1 2 3 4
1 2
1 2
3 4
3 4
1 2 3 4
1 2 3 4
1 2
3 4
TB1
Motor brake
filter (Series C)
Motor thermal
switch filter
(Series C)
Motor brake
filter (Series C)
Motor thermal
switch filter
(Series C)
Motor brake
filter (Series C)
Motor thermal
switch filter
(Series C)
IMPORTANT
The thermal circuit includes filtering on the TB1/TB2
connector board that is rated for 24V only. For TB1/
TB2 wiring alternatives, refer to the table below.
If:
Then:
120V ac is used on the start/stop string
Option 1: Install a 24V pilot relay on the
thermal switch circuit.
Option 2: Bypass the TB1/TB2 terminations
1
.
24V is used on the start/stop string
Follow the wiring shown in Figure A.9 above.
ATTENTION
!
Implementation of safety circuits and risk assessment
is the responsibility of the machine builder. Please
reference international standards EN1050 and EN954
estimation and safety performance categories. For
more information refer to Understanding the
Machinery Directive (publication SHB-900).