Troubleshooting Your 1394 SERCOS Interface System
2-15
DriveHardFault
(Memory Init)
Memory hardware initialization fault detected.
SHUTDOWN
No
DriveHardFault
(NV Mem Init)
Non-volatile memory is corrupt.
SHUTDOWN
No
DriveHardFault
(Objects Init)
Non-volatile memory is corrupt.
SHUTDOWN
No
PowerPhaseLoss
Fault
(Phase Loss Flt
2
)
The three-phase input line is monitored and a fault will be issued
whenever a phase loss is detected.
SHUTDOWN/ STOP No
DriveHardFault
(SCANport Comm)
SCANport/DPI Communication Failed
STOP
No
SERCOSFault
(SERCOS Ring Flt)
SERCOS ring not active after being active and operational.
STOP
No
DriveHardFault
(SERCOS Init)
SERCOS hardware initialization fault detected.
SHUTDOWN
No
DriveHardFault
(Serial Ring Init)
Intermodule serial communication failed.
SHUTDOWN
No
SERCOSFault
(SERCOS Same Addr)
Duplicate node address detected on SERCOS ring.
STOP
No
DriveOvervoltage
Fault
(Shunt Time Out)
Shunt resistor continuous rating exceeded.
SHUTDOWN
No
DriveOvertemp
Fault
(Sys Overtemp)
The 1394 thermal sensor tripped when internal ambient temperature
exceeded rating.
SHUTDOWN
No
DriveHardFault
(Sys Mod Unknown)
Active when serial ring detects unknown system module.
SHUTDOWN
No
DriveHardFault
(Task Init)
Software initialization fault detected.
SHUTDOWN
No
DriveHardFault
(Unknown Fault)
Fault is detected but source is unknown
STOP
No
Fault Message
RSLogix (HIM):
Description:
Drive Fault
Action
RSLogix
Programmable
Fault Action?