Connecting Your 1394 SERCOS Interface System

3-5

Ungrounded Power Configuration

The ungrounded power configuration does not allow for a neutral
ground point. If you determine that you have ungrounded power
distribution in your plant, you need to move the factory installed
jumper to the ungrounded power distribution position to prevent
electrostatic buildup inside the 1394. Refer to the instructions on
page 3-6 for 5 and 10 kW system modules, and starting on page 3-7
for 22 kW system modules.

Figure 3.2
Ungrounded Power Configuration

Note: The input power terminal designated PE is electrically common

to the system module single point bond bar.

Status

U

V

W

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

SERCOS System Module

PE2

W1

V1

U1

PE1

1326 or MP-Series
motor power cable

Cable clamp around shield

Bonded cabinet ground bus

Conduit/4-Wire Cable

Ground grid or

power distribution ground

System module

single point bond bar

Shield

ATTENTION

!

Ungrounded systems do not reference each phase
potential to a power distribution ground. This can
result in an unknown potential to earth ground.