Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 99

Startup
Chapter 6
6-10
Function Checks
Step 15d -- Preset Frequency and Aux Accel/Decel Enable Check
- Motor Disconnected
If three preset speed switches have been installed, verify that switch
SW2 is set to 8SP.
•
Closing switch S1 and opening switches S2 and S3 will force the drive
to 20.00 Hz, the Preset Frequency 2 value set by Parameter 29, within
the 2nd auxiliary accel time set by Parameter 36, or the 2nd auxiliary
decel time set by Parameter 37.
•
Opening switches S1 and S3 and closing switch S2 will force the drive
to 30.00 Hz, the Preset Frequency 3 value set by Parameter 30, within
the 3rd auxiliary accel time set by Parameter 38, or the 3rd auxiliary
decel time set by Parameter 39.
•
Closing switches S1 and S2 and opening switch S3 will force the drive
to 40.00 Hz, the Preset Frequency 4 value set by Parameter 31, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
•
Opening switches S1 and S2 and closing switch S3 will force the drive
to 15.00 Hz, the Preset Frequency 5 value set by Parameter 32, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
•
Opening switch S2 and closing switches S1 and S3 will force the drive
to 25.00 Hz, the Preset Frequency 6 value set by Parameter 33, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
•
Opening switch S2 and closing switches S1 and S3 will force the drive
to 35.00 Hz, the Preset Frequency 7 value set by Parameter 34, within
the 4th auxiliary accel time set by Parameter 40, or the 4th auxiliary
decel time set by Parameter 41.
•
Closing switches S1, S2 and S3 will force the drive to 45.00 Hz, the
Preset Frequency 8 value set by Parameter 35, within the 4th auxiliary
accel time set by Parameter 40, or the 4th auxiliary decel time set by
Parameter 41.