Local/remote control enable – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 57

Operation and Programming
Chapter 5
5-14
Local/Remote Control Enable
Important: If the Remote Operator Station option is installed, Parameter 8
must be set to 1 or 3 to allow remote control.
Parameter 08 -- Local/Remote Control
Units
= Code
Range
= 0/1/2/3
Factory Setting = 0
This parameter enables or disables the drive start, jog, and forward/reverse
functions as follows. The stop button on the Local Control and
Programming Panel will always be functional, but may generate an
OP
error for certain settings detailed below. If installed at the Control and
Signal Wiring Terminal Block, auxiliary input switches S1, S2 and/or S3
will always function as programmed by Parameters 19 and 20 when a valid
start command is present.
If set to 0, local control has been selected. An
L
will be the left-hand letter
shown in the Mode Display. A maintained start command or jumper is not
required at terminals 7 and 8 of the Control and Signal Wiring Terminal
Block.
•
Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.
•
Local jog can be selected by pressing the Shift button.
•
If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.
•
The local stop button will stop the drive as programmed by Parameters
11-14.
•
An auxiliary interlock signal will stop the drive and display either
AU
or
AS
as programmed by Parameter 21.
If set to 1, external 2-wire control has been selected. An
E
will be the
left-hand letter shown in the Mode Display.
•
Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional.
•
An external jog signal will jog the drive and display
EJ
. Local jog
cannot be selected.
•
If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.
•
The local stop button will allow the drive to coast-to-stop and display
OP
.