Operation and Programming
Chapter 5
5-5
The Mode Display
In the programming mode the smaller two-digit display shows the parameter
number selected ––
01
to
62
. Whenever the drive is in the programming
mode, three display items will change.
1. The display will flash.
2. The decimal point normally shown in the lower right hand corner will
disappear.
3. Neither the Hz nor Alternate LED in the Main Display will be lit.
In the monitoring and operating mode the smaller two-digit display shows
the monitoring mode selected ––
•
01
Ć
62
View drive parameters.
•
AO
Monitor drive output current.
•
A1
View equivalent motor RPM.
•
A2
Monitor drive control frequency.
•
LL
,
LE
,
LJ
,
EE
,
EL
or
EJ
The local or remote control source
currently controlling the drive.
LL
To indicate:
1. Drive start, jog, speed and forward/reverse is controlled from the
Local Control Panel.
2. The Local Control Panel stop pushbutton will stop the drive as
programmed by Parameters 11-14.
3. An auxiliary interlock wired to the Control and Signal Wiring
Terminal Block will stop the drive and display either
AU
or
A5
, as set by Parameter 21.
LE
To indicate:
1. Drive start, jog and forward/reverse is controlled from the Local
Control Panel.
2. The Local Control Panel stop pushbutton will stop the drive as
programmed by Parameters 11-14.
3. Drive speed is controlled from a remote reference signal wired
to the Control and Signal Wiring Terminal Block.
4. An external stop signal wired to the Control and Signal Wiring
Terminal Block will allow the drive to coast-to-stop and display
OP
.