Output meter settings, Monitoring mode settings – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 88
Operation and Programming
Chapter 5
5-45
Output Meter Settings
Parameter
55
-- Frequency Output (Amps)
Units
= % of Maximum Output Signal
Range
= 075/125
Factory Setting =
100
This parameter is used to calibrate an output frequency ammeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 1 mA. The 1 mA signal is selected by setting switch SW1 on the
Control Board to the 1 mA position.
Parameter
56
-- Frequency Output (Volts)
Units
= % of Maximum Output Signal
Range
= 075/125
Factory Setting =
100
This parameter is used to calibrate an output frequency voltmeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 10V DC. The 10V DC signal is selected by setting switch SW1 on
the Control Board to the 10V DC position.
Monitoring Mode Settings
Parameter
57
-- Monitor Display Select
Units
= Code
Range
= 0/1/2
Factory Setting = 0
This parameter sets one of three alternate monitoring modes that may be
selected while the drive is running.
When set to 0,
A0
–– monitor equivalent drive output current.
When set to 1,
A1
–– monitor equivalent motor RPM.
When set to 2,
A2
–– monitor drive control frequency.
Parameter
58
-- Motor Pole Select
Units
= Code
Range
= 2/4/6/8/10
Factory Setting = 4
To allow motor RPM to be calculated and displayed when monitoring
mode
A1
is selected, this parameter is used to enter the number of motor
poles.