Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 58
Operation and Programming
Chapter 5
5-15
•
An auxiliary interlock signal will stop the drive and display either
AU
or
AS
as programmed by Parameter 21.
If set to 2, local control has been selected, but a maintained stop command
or jumper must also be present at terminals 8 and 9 of the Control and
Signal Wiring Terminal Block. If not present, all of the following
commands will generate an
OP
error. An
L
will be the left-hand letter
shown in the Mode Display.
•
Both directional start pushbuttons on the Local Control and
Programming Panel will be functional.
•
Local jog can be selected by pressing the Shift button.
•
If Parameter 10 Reverse Lockout is on, only one directional start
pushbutton will be available for jogging or running the drive.
•
The local stop button will stop the drive as programmed by Parameters
11-14.
•
An auxiliary interlock signal will stop the drive and display either
AU
or
AS
as programmed by Parameter 21.
•
An external stop signal at terminals 8 and 9 of the Control and Signal
Wiring Terminal Block will allow the drive to coast-to-stop but display
an
OP
error.
If set to 3, external 3-wire control has been selected. An
E
will be the
left-hand letter shown in the Mode Display.
•
Drive start, jog and forward/reverse is controlled externally through the
Control and Signal Wiring Terminal block. Neither directional start
pushbutton on the Local Control and Programming Panel will be
functional and local jog cannot be selected.
•
An external jog signal will jog the drive and display
EJ
. Local jog
cannot be selected.
•
If Parameter 10 Reverse Lockout is on, only one direction is available
for jogging or running the drive.
•
The local stop button will allow the drive to coast-to-stop and display
OP
.
•
An auxiliary interlock signal will stop the drive and display either
AU
or
AS
as programmed by Parameter 21.