Load requirements, Output power specifications – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 14
Specifications
Chapter 3
3-3
Load Requirements
A balanced 3-phase inductive motor load is typical. Other motor loads may
require application assistance.
Output Power
Waveform:
Sine coded pulse width modulated waveform.
Specifications
Voltage:
Drive Rating ZAA-GAA
0 to applied input voltage, 200V AC,
208V AC,
or 230V AC –– maximum output voltage
cannot exceed applied input voltage.
Drive Rating AAB-CAB
0 to applied input voltage, 380V AC, 415V
AC,
or 460V AC –– maximum output voltage
cannot exceed applied input voltage.
Frequency
Programmable Min and Max Limits
Range:
0 to 400 Hz remote frequency command.
0.5 to 400 Hz local frequency command.
Frequency
±
0.5% of selected maximum output frequency
Regulation:
–10 to +50
°
C ambient temperature range.
Accel/Decel:
Four independently programmable accel times.
Four independently programmable decel times.
Each time may be programmed over a range
from 0.1 to 1600 seconds. If 0 is entered, the
drive will default to 40 ms.
Accel Stall Protection:
140% of rated current.
Decel Stall Protection:
380V DC for 230V AC drive input voltage.
760V DC for 460V AC drive input voltage.
Volts-per-Hertz:
Selectable constant or square v/Hz curves.
DC Boost:
0-40% of maximum output voltage
adjustable in 1% increments.