As shown in figure 4-5 in chapter 4 – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 69
Operation and Programming
Chapter 5
5-26
As shown in Figure 4-5 in Chapter 4 ––
If Parameter 19 = 2 and Parameter 20 = 0
When
and
and
and
Control Board External
External
External
Switch SW2
Switch S1 Switch S2 Switch S3
is Set to
is Set to
is Set to
is Set to
The Parameters Selected are
8SP
OFF
OFF
OFF
None
8SP
ON
OFF
OFF
Preset Frequency 2 + Accel Time 2 + Decel Time 2
8SP
OFF
ON
OFF
Preset Frequency 3 + Accel Time 3 + Decel Time 3
8SP
ON
ON
OFF
Preset Frequency 4 + Accel Time 4 + Decel Time 4
8SP
OFF
OFF
ON
Preset Frequency 5 + Accel Time 1 + Decel Time 1
8SP
ON
OFF
ON
Preset Frequency 6 + Accel Time 1 + Decel Time 1
8SP
OFF
ON
ON
Preset Frequency 7 + Accel Time 1 + Decel Time 1
8SP
ON
ON
ON
Preset Frequency 8 + Accel Time 1 + Decel Time 1
If Parameter 19 = 1 and Parameter 20 = 0
When
and
and
and
Control Board External
External
External
Switch SW2
Switch S1 Switch S2 Switch S3
is Set to
is Set to
is Set to
is Set to
The Parameters Selected are
8SP
OFF
OFF
OFF
None
8SP
ON
OFF
OFF
Accel Time 2 + Decel Time 2
8SP
OFF
ON
OFF
Accel Time 3 + Decel Time 3
8SP
ON
ON
OFF
Accel Time 4 + Decel Time 4
8SP
OFF
OFF
ON
Accel Time 1 + Decel Time 1
8SP
ON
OFF
ON
Accel Time 1 + Decel Time 1
8SP
OFF
ON
ON
Accel Time 1 + Decel Time 1
8SP
ON
ON
ON
Accel Time 1 + Decel Time 1
If Parameter 19 = 0 and Parameter 20 = 0
When
and
and
and
Control Board External
External
External
Switch SW2
Switch S1 Switch S2 Switch S3
is Set to
is Set to
is Set to
is Set to
The Parameters Selected are
8SP
OFF
OFF
OFF
None
8SP
ON
OFF
OFF
Preset Frequency 2
8SP
OFF
ON
OFF
Preset Frequency 3
8SP
ON
ON
OFF
Preset Frequency 4
8SP
OFF
OFF
ON
Preset Frequency 5
8SP
ON
OFF
ON
Preset Frequency 6
8SP
OFF
ON
ON
Preset Frequency 7
8SP
ON
ON
ON
Preset Frequency 8