Function checks - motor disconnected – Rockwell Automation 1333 Drive, 3/4-5HP, 230-575V Series D User Manual
Page 94
![background image](/manuals/578516/94/background.png)
Startup
Chapter 6
6-5
Hz LED
Alternate LED
The Enter Pushbutton
The Stop Pushbutton
The Shift Pushbutton
The Increment Pushbutton
The Mode Display
The Lock Switch
The Directional Start Pushbutons
The Select Pushbutton
The Decrement Pushbutton
The Main Display
Function Checks
- Motor Disconnected
Figure 6Ć3 -- 3/4Ć20ĂHP (.55Ć15kW) Controls
Step 5 -- Local/Remote Control Enable Check
Max Speed Settings Check
Start the drive by pressing either directional start pushbutton. The
pushbutton will light. Press and hold the increment pushbutton and watch
the display increase. Release thew pushbutton when the display reaches
60.00
Hz or maximum speed.
Step 6 -- Monitor Mode Settings Check
Press the select pushbutton once. The main display will flash and show the
last manual set speed entered.
Press the select pushbutton again.
A0.
will be shown in the mode display,
drive output amps in the main display, as set by Parameter 57.
Press the select pushbutton again. The mode display will flash and show
0ĂI.
to indicate the parameter being viewed, and the main display will show
005.0
, the accel time set by Parameter 1.
Press the pushbutton again and
60.00Ă
Hz will again be displayed.
Step 7 -- Reverse Enable Check
Accel and Decel Settings Check
Press the other directional start pushbutton. The pushbutton will light and
the drive display will ramp down to
0.00
Hz within the decel time set by
Parameter 2, then immediately ramp up to
60.00
Hz, the maximum speed
presently programmed by Parameter 3, within the accel time set by
Parameter 1. Reversing is enabled or disabled by Parameter 10.