Create and collect a user-defined point – Rockwell Automation 1441-DYN25-Z Dynamix 2500 Data Collector User Manual
Page 152

152
Rockwell Automation Publication 1441-UM001B-EN-P - September 2012
Chapter 5
Collecting and Reviewing Data
Create and Collect a User-defined Point
The Offroute program lets set up and collect any type of Offroute measurement
point. The Dynamix 2500 data collector keeps the user-defined parameters until
you collect another measurement point or press F2 (Default) on the Offroute
User screen.
Table 42 - Types of Offroute Measurements
Type
Description
Same
The measurement configuration is based upon the most recently selected
measurement in the Route Manager. The setup is the same as the active
measurement. This lets you collect Offroute measurements that are identical to
your active measurement, but from various sensor positions for analysis purposes.
If you have setup the active route to collect both FFT and time waveform data, the
Offroute Same measurement is FFT only.
Measurement parameters are set to:
Overlap – 50%
Bin Zeroing – On
Opposite
The measurement configuration is based upon the most recently selected
measurement in the Route Manager, except it collects the Opposite data format.
For example, if the active Route Point collects FFT spectrum data, the Opposite
Offroute measurement collects time waveform data, and vice versa.
Measurement parameters are set to:
Overlap – 50%
Bin Zeroing – On
For Accel, Velocity, Accel Time, and gE pre-set measurement types, the following
standard settings are taken from the current selected Route measurement:
– Sensitivity
– Coupling
– Detection
– Window
Accel
Performs a standard vibration Acceleration measurement.
These are the settings for the measurement parameters.
Parameter
Value
Display Format
Spectrum
Units - Accel
Accel (G)
Input Channel
X
High-pass frequency
1.1 Hz
Fmax
10 kHz
Lines/Samples
800 Lines
Averages
4
Overlap
50%
Type
Spectral
Ext. Trigger Slope
Positive
Trigger Level
2 V
Bin Zeroing
On