Safety engineering, Safe bus interfaces profisafe connection – Lenze E94AYAE SM301 User Manual
Page 98

Safety engineering
Safe bus interfaces
PROFIsafe connection
l
98
EDS94AYAE EN 7.0
Status byte
For the PROFIsafe V1 mode only the indicated bits of the PROFIsafe status byte are
supported:
Assignment
Bit
Byte
7
6
5
4
3
2
1
0
4
−
−
−
FV_activated
COM−Failure WD-Timeout
COM−Failure CRC
−
−
Tab. 1−13
Structure of the PROFIsafe status byte in V1 mode
Bit coding − status byte
Bit
Name
Description
2
COM−Failure CRC
Status after communication error is active.
3
COM−Failure
WD-Timeout
Status after time−out is active.
4
FV_activated
The PROFIsafe input data is deactivated.
−
Reserved for future extensions
Tab. 1−14
Detailed specification of the status byte in V1 mode
For the PROFIsafe V2 mode only the indicated bits of the PROFIsafe status byte are
supported:
Assignment
Bit
Byte
7
6
5
4
3
2
1
0
4
−
cons_nr_R
Toggle_d
FV_activated
WD_timeout
CE_CRC
−
−
Tab. 1−15
Structure of the PROFIsafe status byte in V2 mode
Bit coding − status byte
Bit
Name
Description
2
CE_CRC
Status after communication error is active.
3
WD_timeout
Status after time−out is active.
4
FV_activated
The PROFIsafe input data is deactivated.
5
Toggle_d
Change shows increase of the consecutive number.
6
cons_nr_R
Consecutive number has been reset.
−
Reserved for future extensions
Tab. 1−16
Detailed specification of the status byte in V2 mode