Safety engineering
Safety functions
Safe operation mode selector
l
82
EDS94AYAE EN 7.0
Codes
Parameter:
Name:
Data type:
Index:
C15200
OMS: Stop function
UNSIGNED_8
9375
d
= 249F
h
Selection of the stop function in special operation
Selection list
(Lenze setting bold)
Information
0 STO
Safe torque off
1 SS1
Safe stop 1
2 SS2
Safe stop 2
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15201
OMS: motion function
UNSIGNED_8
9374
d
= 249E
h
Selection of the motion function in special operation
Selection list
(Lenze setting bold)
Info
3 SLS1
Safely limited speed 1
(Lenze setting up to SM301 V1.3)
4 SLS2
Safely limited speed 2
(From SM301 V1.1)
5 SLS3
Safely limited speed 3
(From SM301 V1.1)
6 SLS4
Safely limited speed 4
(as of SM301 V1.1)
11 Free traversing
(Lenze setting from SM301 V1.4)
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
I
Tip!
If SLSx has been parameterised as the motion function during special
operation, a change to the acceptance operation is not possible until the
reduced speed is monitored and maintained (SLSx monitored).
C15202
OMS: Function at LOW level
UNSIGNED_8
9373
d
= 249D
h
Function that is executed in case of LOW level at the safe input with OMS function.
Caution: According to the closed−circuit principle, the parameterisation must not cause any additional danger.
Selection list
(read only)
Information
0 Normal operation
(From SM301 V1.3)
1 Special operation
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15203
SLI: Safely lim. increment
UNSIGNED_32
9372
d
= 249C
h
Number of increments for safely limited increment
Setting range
(min. value | unit | max. value)
Information
0
Incr.
2147483647 Lenze: 1, deactivate: 0
(From SM301 V1.4)
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15204
SLI: Amount of position change
UNSIGNED_32
9371
d
= 249B
h
Maximum position change while SLI is active.
Display area
(min. value | unit | max. value)
Information
0
Incr.
2147483647
(From SM301 V1.4)
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer