1.3.12
Safe enable switch
1.3.12.1
Description
Enable Switch / ES
The drive can be traversed in special operation using an enable switch (see operation mode
selector).
1.3.12.2
Conditions
A safe input must be parameterised and interconnected as enable switch. You can only
connect and parameterise one enable switch. The ES bit of the safety bus must be
deactivated (C15113).
The enable switch function can also be selected via the safety bus with the ES bit, unless
a safe input is parameterised as enable switch.
The special operation must be activated.
The plausibility check rejects ambiguous settings until they are parameterised correctly.
Codes
Parameter:
Name:
Data type:
Index:
C15031
SD-In sensor function
UNSIGNED_8
9544
d
= 2548
h
Function configuration of the safe inputs.
l
The "operation mode selector" and "enable switch" functions may only be assigned to one of the four safe
inputs.
Selection list
(Lenze setting printed in bold)
Information
0 Free assignment
Safety function set in C15032
1 Emergency stop
Safe stop emergency function (SSE)
2 Operation mode selector
Safe operation mode selector (OMS)
3 Enable switch
Safe enable switch (ES)
Subcodes
Information
C15031/1
SD-In1 sensor function
C15031/2
SD-In2 sensor function
C15031/3
SD-In3 sensor function
C15031/4
SD-In4 sensor function
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
1.3.12.3
Activation
How to activate the function:
ƒ
Via a safe input which has been assigned to the function by parameterisation. With
the edge change 0−1 of the ES signal, the status changes to "Acceptance (ES)".
Only if no safe input is used, the function can only be activated via the safety bus:
ƒ
A data telegram with corresponding contents must be transmitted to the standard
device (edge change 0−1 of the ES signal).