Safety engineering, Appendix module error messages – Lenze E94AYAE SM301 User Manual
Page 136

Safety engineering
Appendix
Module error messages
l
136
EDS94AYAE EN 7.0
Error type/response/
Note
Description
Field
Error type/response/
Note
Description
Error number
Test functions − inputs
144
0x90
Stuck at High SD−In1, channel A
(Short circuit (High)
Trouble/−
SD−In1: OFF state
145
0x91
Stuck at High SD−In1, channel B
146
0x92
Stuck at High SD−In2, channel A
Trouble/−
SD−In2: OFF state
147
0x93
Stuck at High SD−In2, channel B
148
0x94
Stuck at High SD−In3, channel A
Trouble/−
SD−In3: OFF state
149
0x95
Stuck at High SD−In3, channel B
150
0x96
Stuck at High SD−In4, channel A
Trouble/−
SD−In4: OFF state
151
0x97
Stuck at High SD−In4, channel B
154
0x9A
CLA/CLB short circuit
Short circuit between the CLA and CLB clock outputs
Trouble/−
SD−In: OFF state
Safe parameterisation
160
0xA0
New parameter set deleted
(by the safe parameter setting in the Engineer)
−/−
Logbook entry: Info
161
0xA1
New safe parameter set loaded
(by the safe parameter setting in the Engineer or the procedure
with the module switch)
162
0xA2
Memory module parameter set − access error
(Error while accessing the parameter set of the memory module.)
Trouble/STO
OFF state for all SD−In and
SD−Out
163
0xA3
Different parameter sets
(in the memory module and SM301)
164
0xA4
No safe parameter set in the safety module
(SM301 has no parameter set.)
165
0xA5
Defective parameter set
(SM301 parameter set is defective.)
166
0xA6
Parameter set in memory module − format error
(Format error in parameter set of memory module)
167
0xA7
Parameter set − plausibility error
168
0xA8
Parameter set − communication error
(Communication error when loading the parameter set)
169
0xA9
Module ID does not equal effective safety address
(Module ID in the parameter set does not equal the effective
safety address)
Warning/STO
OFF state for all SD−In and
SD−Out
Test functions − internal module
192
0xC0
Reference voltage error
Trouble/STO
OFF state for all SD−In and
SD−Out
193
0xC1
6 V voltage error
194
0xC2
5 V voltage error
195
0xC3
2.6 V voltage error
208 0xD0
Safe speed is invalid
Trouble/STO
209 0xD1
SSM: Encoder error
Trouble/STO
210 0xD2
SSM: Resolver error
Trouble/STO
211 0xD3
SSM: Standard device data error
Trouble/STO
212 0xD4
SSM: Speed comparison error
213 0xD5
SSM: Synchronisation error
214 0xD6
SSM: Wrong PDO version
Trouble/STO
Tab. 1−24
Description of the numerical entries