Safety engineering, Appendix module internal codes – Lenze E94AYAE SM301 User Manual
Page 114

Safety engineering
Appendix
Module internal codes
l
114
EDS94AYAE EN 7.0
Index:
Data type:
Name:
Parameter:
C15003
Command status
UNSIGNED_16
9572
d
= 2564
h
Status of the current command.
l
In high byte the command is repeated.
l
In low byte the status is displayed:
0x00:
no command
0x01:
command executed
0x02:
password invalid
0x03:
command in process
0x04:
command unknown
0x05:
command error
Display area
(min. value | unit | max. value)
Information
0
2309
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15010
Parameter set status
UNSIGNED_8
9565
d
= 255D
h
Status of the parameter set
Selection list
(read only)
Information
0 No parameter set
1 Parameter set valid
2 Read error − memory module
3 Parameter set dissimilar
4 CRC error
5 Version error
6 Format error
7 Plausibility error
8 Assignment error
9 Local read error
10 Communication error GG
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15011
Parameter CRC
UNSIGNED_32
9564
d
= 255C
h
Parameter checksum (CRC = Cyclic Redundancy Code)
Display area
(min. value | unit | max. value)
Information
0
4294967295
Subcodes
Information
C15011/1
CRC safety module
C15011/2
CRC memory module
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15013
Time for parameter set creation
UNSIGNED_64
9562
d
= 255A
h
Time of parameter set creation
Display area
(min. value | unit | max. value)
Information
0
1844674407370
96E+19
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15014
Time − RTC parameter setting
VISIBLE_STRING
9561
d
= 2559
h
Time of parameter set transfer from the memory module as a value of the real−time clock (RTC).
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer
C15015
Time sec. parameter setting
UNSIGNED_32
9560
d
= 2558
h
Time of parameter set transfer from the memory module as a value of the power−on time meter from the
controller.
Display area
(min. value | unit | max. value)
Information
0
S
4294967295
þ Read access o Write access o Controller inhibit o PLC-STOP o No transfer