Safety engineering, Safety functions safe stop 1, Codes – Lenze E94AYAE SM301 User Manual
Page 58

Safety engineering
Safety functions
Safe stop 1
l
58
EDS94AYAE EN 7.0
Codes
Parameter:
Name:
Data type:
Index:
C15300
Restart behaviour
UNSIGNED_8
9275
d
= 243B
h
Behaviour for restart after functions have been cancelled
Selection list
(Lenze setting bold)
Information
0 Acknowledged restart
1 Automatic restart
Subcodes
Information
C15300/1
Restart - STO, SS1
C15300/2
Restart - SS2, SOS
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15305
SS1, SS2: Stopping time
UNSIGNED_16
9270
d
= 2436
h
Stopping time for the SS1 and SS2 safety functions
Setting range
(min. value | unit | max. value)
Information
0
MS
30000 Lenze: 0, increment: 2 ms
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15306
SS1 mode
UNSIGNED_8
9269
d
= 2435
h
Selection list
(Lenze setting bold)
Information
0 STO after stopping time
(From SM301 V1.3)
1 STO at n = 0
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15307
SS1: Deceleration STO after n=0
UNSIGNED_16
9268
d
= 2434
h
Display area
(min. value | unit | max. value)
Information
0
ms
30000 Lenze: 0, increment: 2 ms
(From SM301 V1.3)
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15310
Tolerance window (n=0)
INTEGER_16
9265
d
= 2431
h
Safely monitored tolerance window for zero speed
Setting range
(min. value | unit | max. value)
Information
0
rpm
16000 Lenze: 0
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer