Safe torque off, Safety engineering, Safety functions safe torque off – Lenze E94AYAE SM301 User Manual
Page 54
Safety engineering
Safety functions
Safe torque off
l
54
EDS94AYAE EN 7.0
1.3.3
Safe torque off
1.3.3.1
Description
Safe Torque Off/STO
This function corresponds to a "Stop 0" according to EN 60204.
When this function is used, the power supply of the motor is immediately (t1) safely
interrupted. The motor cannot create a torque and thus no dangerous movements of the
drive can occur. Additional measures, e.g. mechanical brakes are needed against
movements caused by external force.
t
t
n
0
0
1
2
t1
I
STO
t1
t
0
I
0
SM301DIA_STO
0 Input signal of the request of a safety function
I
ON state
O OFF state
1 Speed characteristic n of the motor
t
Time axis
tx Action instant
2 Feedback(s)
The restart behaviour can be set (C15300/1). Function sequence and error response have
no adjustable parameters.
Codes
Parameter:
Name:
Data type:
Index:
C15300
Restart behaviour
UNSIGNED_8
9275
d
= 243B
h
Behaviour for restart after functions have been cancelled
Selection list
(Lenze setting bold)
Information
0 Acknowledged restart
1 Automatic restart
Subcodes
Information
C15300/1
Restart - STO, SS1
C15300/2
Restart - SS2, SOS
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer