Safety engineering
Device modules
SM301 safety module
l
21
EDS94AYAE EN 7.0
Displays
Pos.
Colour
State
Description
MS
(Module State)
Green
On
Drive−based safety has initialised without a fault.
Blinking
Drive−based safety has initialised without a fault. Internal
communication to the standard device is not possible.
Flashing
Drive−based safety is in service status.
For exiting, parameterise the drive−based safety.
Off
Drive−based safety is not initialised.
Acknowledgement is not possible.
EN
(Enable)
Yellow
On
Controller enabled
Off
Non−safe display "STO"
ME
(Module Error)
Red
On
System error
Blinking
Trouble
Flashing
Warning
Off
Error−free operation
AS
(Acknowledge Stop)
Yellow
On
Request of an acknowledgement for the restart or the
parameter set adoption
Blinking
SS1/STO active
Flashing
SS2/SOS active
Off
No stop function active
BE
(Bus Error)
Red
On
Safety bus error:
l
Communication is not possible.
l
Acknowledgement is possible.
Blinking
Safety bus error: no valid configuration.
Off
Safety bus: error−free operation.
DE
(Drive Error)
Red
On
Drive−based safety is not accepted by the standard device
(see notes in the instructions for the standard device).
Off
Drive−based safety is correctly recognised by the standard
device.