Safety engineering, Safety functions safely limited speed, 2 activation how to activate the function – Lenze E94AYAE SM301 User Manual
Page 73

Safety engineering
Safety functions
Safely limited speed
l
73
EDS94AYAE EN 7.0
Index:
Data type:
Name:
Parameter:
C15333
SLS: Permissible direction of movement
UNSIGNED_8
9242
d
= 241A
h
Permissible direction of movement during SLS monitoring
Selection list
(Lenze setting printed in bold)
Information
0 Both directions enabled
1 Positive direction enabled
2 Negative direction enabled
Subcodes
Information
C15333/1
SLS1: Permissible direction of movement
(from SM301
V1.3)
C15333/2
SLS2: Permissible direction of movement
(from SM301
V1.3)
C15333/3
SLS3: Permissible direction of movement
(from SM301
V1.3)
C15333/4
SLS4: Permissible direction of movement
(from SM301
V1.3)
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
C15350
SLS, SMS: Max. response time
UNSIGNED_16
9225
d
= 2409
h
Maximum time after an exceeded speed has been detected, after which the speed must be below the limit
again.
Setting range
(min. value | unit | max. value)
Information
0
MS
30000 Lenze: 0, increment: 2 ms
þ Read access } Write access o Controller inhibit o PLC-STOP o No transfer
1.3.9.2
Activation
How to activate the function:
ƒ
"OFF state" at a safe input, the function of which has been assigned by parameter
setting.
ƒ
Via a safety bus data telegram with corresponding content.
1.3.9.3
Fault analysis
The fault analysis is described with the SMS function (
¶ 69).