Safe output, Safety engineering – Lenze E94AYAE SM301 User Manual
Page 37

Safety engineering
Device modules
Safe output
l
37
EDS94AYAE EN 7.0
1.2.5
Safe output
1.2.5.1
General
Via the safe output O1A/O1B information can be output to a higher−level unit (e.g. safety
PLC) or external switching elements (actuators) can be controlled.
The feedback output is designed in a potential−free fashion. If electrical isolation is
required, a separate supply line must be used.
ƒ
The status of the safe output is controlled via two ways:
– directly from the safety module (parameter setting required)
– via the PROFIsafe output data
ƒ
The safe output is PP switching, i.e. two plus channels are switched.
ƒ
The safe output in ON state is cyclically tested by quick LOW switching.
– The A and B channels are tested at different times in cycles of approx. 2 s, with
test pulses of < 1 ms.
– When selecting the downstream control elements, ensure that the test pulses will
not be detected as LOW signal.
These errors will be detected and set the output to OFF state:
ƒ
Short circuit to supply voltage.
ƒ
In the ON state: Short circuit between the output signals.
ƒ
IN the OFF state: Missing 24−V supply voltage at the terminal 24O is detected as
"Stuck−at−Low" error.
These errors are not detected:
ƒ
In the OFF state: short circuit between the output signals.
The output can be assigned multiple feedback information by parameter setting:
ƒ
Status of the safety function
ƒ
Information on error responses
The code C15060 contains information on the status of the feedback output.
Additional conditions for SM301 from version VB 1.1 onwards:
ƒ
With active cascading in C15035 the SD−Out1 output cannot be used freely
anymore.