Terminate auxiliary power – ETC Unison ERn Rack-mount Control Enclosure User Manual
Page 21

3
Connect Wiring
17
Step 3:
Remove the LinkPower connector (labeled LON).
•
Notice the LinkPower/LON connector is
labeled to indicate that the connector is split
between two LON segments, allowing three
station wire home runs per segment. This is
effective only when a Paradigm dual station
repeater module (P-DREP) is used. With the
standard Paradigm station repeater module
(P-REP) you may connect up to six station
home runs to the connector for the single LON
segment control.
Step 4:
Loosen the terminal screws for as many wire pairs
you are terminating. Keep in mind that the
connector is split into two LON segments. Be sure
to terminate each wire pair to the correct segment.
Step 5:
Insert each white (typical) wire from the pairs into an “A” terminal on the
connector and tighten the screw firmly to secure the wire into the connector.
Step 6:
Insert each black (typical) wire from the pairs into an “B” terminal on the
connector and tighten the screw firmly to secure the wire into the connector.
Step 7:
The 14 AWG (2.5mm
2
) ground wire can terminate to the ground bus located on
the rear panel of the ERn enclosure. Connect the other end of the ground wire to
the green/yellow striped wire connected at the architectural control station using
a Scotchlok connector. Reference the related
station installation manual
for
further details.
Step 8:
Replace the connector to the rear panel I/O.
Terminate Auxiliary Power
Auxiliary power is required when you are installing powered Unison control stations. ETC
recommends using two 16 AWG (1.5mm
2
) stranded wires for 24 Vdc auxiliary power to the
control station(s). Auxiliary power is topology-free. Maximum auxiliary voltage runs are
dependant by the wire gauge and the distribution of auxiliary load determined by each
installation. the auxiliary supply is capable of 36W (1.5A at 24 Vdc).
The auxiliary power connector (labeled Aux Power) provides
termination for up to 20 wires in the ten position pluggable
connector. Each terminal allows up to two 16 AWG (1.5mm
2
)
wire and provides 24 Vdc power to Unison control stations when
used with the Paradigm ACP.
Step 1:
Pull auxiliary control power wiring (typically 16 AWG
(1.5mm
2
) red / black wire pair) to the ERn enclosure
rear panel.
Step 2:
Strip 3/16” (5mm) of insulation from the ends of each
wire pair.
Step 3:
Remove the auxiliary power connector from the I/O
board.
Step 4:
Loosen the terminal screws for as many auxiliary wire
pairs as you are terminating.
Step 5:
Insert the black (typical) auxiliary power wire from the pair into a “-” terminal on
the connector and tighten the screw to secure the wire into the connector.
Step 6:
Insert the red (typical) auxiliary power wire from the pair into a “+” terminal on the
connectors and tighten the screw to secure the wire into the connector.
Step 7:
Repeat steps 5 and 6 for all auxiliary power wires in the enclosure.
Step 8:
Replace the connector to the rear panel I/O.
1A
1B
1A
1B
1A
1B
2A
2B
2A
2B
2A
2B
-
+
-
+
-
+
-
+
-
+