beautypg.com

Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 9

background image

7

95-8656

4.2

WirinG

POwER SUPPLY REQUIREmENTS
Calculate the total gas detection system power

consumption rate in watts from cold start-up. Select a

power supply with adequate capability for the calculated

load. Ensure that the selected power supply provides

regulated and filtered 24 Vdc output power for the entire

system. If a back-up power system is required, a float-type

battery charging system is recommended. If an existing

source of 24 Vdc power is being utilized, verify that system

requirements are met. The acceptable voltage range is

18-30 Vdc measured at the input to the UD10-DCU.

wIRINg CabLE REQUIREmENTS
Always use proper cabling type and diameter for input

power as well as output signal wiring. 14 to 18 AWG

shielded stranded copper wire is recommended. Correct

wire size depends on the device and wire length. Refer to

the appropriate Appendix for additional information. The

maximum cable length from power source to UD10-DCU

is 2000 feet. Maximum cable length from UD10-DCU to

sensor is 2000 feet.

noTe

The use of shielded cable in conduit or shielded
armored cable is highly recommended. In
applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and
non-signaling conductors to prevent nuisance
eMI problems.

CautIon

The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.

wIRINg PROCEDURE

noTe

Since the UD10-DCU can be used with a variety
of different detection devices, information that
is specific to each detector model (wiring,
calibration, HART menus, etc.) is covered in an
Appendix that is dedicated to that device. Refer
to the appropriate Appendix at the back of this
manual for specific information when wiring the
detection system. For information on devices
not covered in an Appendix, refer to the manual
provided by the device’s manufacturer.

Connect 24 vdc power lead wires and communication

network cable to the appropriate terminal block. Refer

to Figure 2 for an illustration of the UD10-DCU wiring

terminal board.

COM 1 - Communication network connections:

Connect to COM 2 terminals of the next

device on the loop, A to A and B to B.

COM 2 - Communication network connections:

Connect to COM 1 terminals of the previous

device on the loop, A to A and B to B.

24 VDC - Connect the “+” terminal to the positive

side of the 24 vdc power source. (Both “+”

terminals are connected internally.)

Connect the “–” terminal to the negative

side of the 24 vdc power source. (Both “–”

terminals are connected internally.)

Figure 3 shows a UD10-DCU Wired to a generic

sensing device. Refer to the appropriate Appendix for

information regarding a specific detector.

grease/Lubrication
To ease installation and future removal, ensure that all

junction box covers and sensor threads are properly

lubricated. If the need arises for additional lubrication,

use either Lubriplate grease (see Ordering Information

for part number) or Teflon tape. Avoid the use of silicone

grease.

ShIELD CONNECTIONS
The UD10 provides terminals for proper grounding of

wiring cable shields (located on the sensor, 4-20 mA,

and operating power terminal blocks). These shield

terminals are not connected internally, but are connected

to ground through capacitors. The capacitors ensure an

RF ground, while preventing 50/60 Hz ground loops.

Ground all shields as shown in the wiring examples

throughout this manual.

Important

For proper grounding, all junction boxes / metal
enclosures must be connected to earth ground.

The following are required for installations requiring CE

Mark compliance:
• For shielded cable installed in conduit, attach the wire

shields to the “shield” connections on the terminal

blocks, or to earth ground on the case.

• For installations without conduit, use double shielded

cable. Terminate the outer shield to earth ground on

the case. Terminate the inner shield to the “shield”

connection on the terminal blocks.