Appendix l – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual
Page 58
4.2
95-8656
L-1
AppenDix l
UD10-DCU with mODEL CgS COmbUSTIbLE gaS SENSOR
WirinG
importAnt notes
noTe
The UD10-DCU with CGS Interface option and
CGS sensor is certified as a “Gas Detector”
and performance approved to standards
FM6310/6320, ATeX 60079-29-1, and IeC
60079-29-1.
noTe
only Constant Current type CGS sensors may be
used with the UD10.
CautIon
The sintered metal flame arrestor is an integral
part of the combustible gas sensor. Do noT
operate the gas detector if the flame arrestor is
damaged or missing, since the exposed element
is a potential ignition source.
CautIon
Silicone based lubricants must never be used on
or near the CGS sensor, since this can result in
irreversible damage to the sensing element.
CautIon
When the UD10-DCU is configured for a
non-latching high alarm, the eQP Controller must
always latch and require a deliberate manual
action to clear a high gas alarm.
4000
3500
3000
2500
2000
1500
1000
500
0
18
19
20
21
22
23
24
25
26
27
28
29
30
Power Supply Voltage
Dist
ance in f
t.
UD10-DCU with PIRECL/OPECL/NTMOS/CGS
12
14
16
18
AWG
Wire Size
Notes: Maximum cable length from power source to UD10 is 2000 feet.
Maximum cable length from UD10 to CGS sensor is 500 feet
(using 16 AWG cable minimum).