Calibration – Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual

Page 31

background image

F-3

95-8656

4.2

cAlibrAtion

gT3000 wITh TOxIC gaS SENSOR

From gT3000:
1. Using the magnet, activate the magnetic calibration

switch on the GT3000. The green LED turns to

yellow.

MAGNETIC

SWITCH

LED

A2443

Location of Magnetic Switch on GT3000

2. The UD10-DCU will display “Waiting for Zero” on

the main display screen, with the yellow LED on the

detector housing illuminated continuously.

3. The UD10-DCU will then display “Waiting for Signal”

on the screen, while the yellow LED on the detector

is flashing.

4. The UD10-DCU will display “Waiting for Gas” on

the screen, while the yellow LED on the detector is

flashing.

5. Apply calibration gas to the sensor.

6. The UD10-DCU will display “Waiting for Span” on

the screen, while the yellow LED on the detector is

flashing.

7. When the UD10-DCU displays “Remove Cal Gas”

on the screen and all LEDs on the detector housing

are off, remove the calibration gas.

8. After successful calibration, the UD10-DCU

automatically returns to the normal display with the

green LED illuminated on the detector.

From UD10-DCU
1. Using the magnet to activate the switches on the

UD10-DCU display, navigate to the Calibration

menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Cal

Cal Gas Conc
Calibration
Change Snsr Type

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10-DCU will display “Waiting for Zero” on

the main display screen, with the yellow LED on the

detector housing illuminated continuously.

4. The UD10-DCU will then display “Waiting for Gas”

on the screen, while the yellow LED on the detector

is flashing.

5. Apply calibration gas to the sensor.

6. The UD10-DCU will display “Waiting for Span” on

the screen, while the yellow LED on the detector is

flashing.

7. When the UD10-DCU displays “Remove Cal Gas”

on the screen and the LEDs on the detector housing

are off, remove the calibration gas.

8. After completion of a successful calibration, the

UD10-DCU automatically returns to the normal mode

with the green LED illuminated on the detector.