Det-Tronics UD10 DCU Emulator FlexVu Universal Display Unit User Manual
Page 6
4
95-8656
4.2
aLaRmS
The UD10-DCU has a low and high alarm that are set
from the S3 configuration software and then downloaded
to the UD10-DCU. Alarm status can be viewed at the
UD10-DCU display, the EQP controller, or S3. Alarms
are non-latching at the UD10-DCU, but can be latched
using logic within the EQP Controller.
With some configurations, the alarm limits on the
UD10-DCU are tighter than on S3. If a value is out of
range, the UD10-DCU will set the value as close as
possible while remaining within the allowable range (See
Table 1). After the configuration download is complete,
the alarm setpoints can be viewed at the UD10-DCU
under Display Status->LON Config menu.
CaLIbRaTION gaS CONCENTRaTION
The calibration gas concentration is programmed
from S3 and downloaded to the UD10-DCU. See
Table 2 for calibration gas limits. NTMOS, CGS, and
PIR9400 require a gas concentration of 50% full scale.
Calibration gas concentration can be viewed from the
UD10-DCU menu under Display Status->LON Config.
Detector Type
UD10 Limits
Recommended EQP
Configuration
EQP Limits
System Limits
GT3000 Toxic
30-90%
Universal Automatic
20-100%
30-90%
GT3000 O2
20.9% v/v
Oxygen
5-25% v/v
20.9% v/v
PIR9400
50%
Explosive
20-100%
50%
Eclipse
30-90%
Explosive
20-100%
30-90%
Open Path
30-90%
Universal Automatic
20-100%
30-90%
C706x
30-90%
Universal Automatic
20-100%
30-90%
505/CGS
N/A
Explosive
20-100%
N/A
NTMOS H2S
50%
Universal Automatic
20-100%
50%
CGS
50%
Explosive
20-100%
50%
Generic Device
N/A
Universal Automatic
20-100%
20-100%
Table 2—Calibration Gas Concentration Limits
UD10 Limits
EQP Limits
System Limits
Detector Type Low alarm
high alarm
Recommended
EQP Configuration
Low alarm high alarm Low alarm high alarm
GT3000 Toxic
5-50%
10-90%
Universal Automatic
10-100%
20-100%
10-50%
20-90%
GT3000 O2
*
16-20.5% v/v 5-20.5% v/v
Oxygen
1.3-25% v/v 2.5-25% v/v 16-20.5% v/v 5-20.5% v/v
PIR9400
5-50%
10-60%
Explosive
5-40%
10-60%
5-40%
10-60%
Eclipse
5-50%
10-60%
Explosive
5-40%
10-60%
5-40%
10-60%
Open Path
5-50%
10-90%
Universal Automatic
10-100%
20-100%
10-50%
20-90%
C706x
5-50%
10-90%
Universal Automatic
10-100%
20-100%
10-50%
20-90%
505/CGS
5-50%
10-60%
Explosive
5-40%
10-60%
5-40%
10-60%
NTMOS H2S
5-50%
10-90%
Universal Automatic
10-100%
20-100%
10-50%
20-90%
CGS
5-50%
10-60%
Explosive
5-40%
10-60%
5-40%
10-60%
Generic Device
0-100%
0-100%
Universal Automatic
10-100%
20-100%
10-100%
20-100%
Table 1—UD10-DCU Alarm Limits
*
Sensor approved for oxygen depletion (<21% V/V) only.